Permit Information
Permit NumberELE09-00636
StatusFinaled
Name ROMAR ELECTRIC
Site Address 3494 S TK AVE
Project Name 
Customer NumberE19557
ePlanReview 
Description
Electrical Permit - New: Warehouse freezer lines, drop cords, lighting, additional panels & office remodel.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (ELE)  6/1/2016 DONE
Second Notice 10/2/200910/2/2009 DONE
Third Notice 10/2/200910/2/2009 DONE
First Notice6/19/20096/19/200910/2/2009 DONE
DetailsJack Frank
Final6/19/20096/19/20096/19/2009PPASS
DetailsJack Frank
Skip Phone #: ###-#### ok card signed
Final6/12/20096/12/20096/12/2009PPART
DetailsJack Frank
Tim Phone #: ###-#### t/o ok still needs labels 210.5
Final6/9/20096/10/20096/12/2009ANR
DetailsJack Frank
tim Phone #: ###-#### called needsID of more than one voltage present 210.5 corner grded delta grounded conductor shall be white or gray 200.6 bonding for xformer secondary side min #8 250.66
Electrical Rough-In6/3/20096/3/20096/3/2009PPART
DetailsJack Frank
field evaluation for refer units ok
Conference6/3/20096/3/20096/3/2009PDONE
DetailsJack Frank
needs grding for xformers and p/s load side xformers
Electrical Rough-In6/2/20096/3/20096/3/2009APART
DetailsJack Frank
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae grd for xformers, p/s rated disconnect secondary side called
Conference5/19/20095/19/20095/19/2009ADONE
DetailsJack Frank
conference with UL and contr about refer units
Permanent Service4/27/20094/28/20094/28/2009APASS
DetailsMike Kinnear
tim Phone #: ###-#### p/s u/g reconnect ok survey needs factory bonding jumper in main panel
Permanent Service4/22/20094/23/20094/23/2009ANR
DetailsMike Kinnear
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae t/w tim job not ready all disconnects need to be grouped
Conference4/20/20094/20/20094/20/2009PDONE
DetailsMike Kinnear
Tim Phone #: ###-#### ok conf. regarding all electrical equipment which needs to be listed & labled
Electrical Rough-In4/15/20094/15/20094/15/2009PPART
DetailsJack Frank
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae r/i ok 1 wall downstairs, corr posted to BLD09-00326, no violations retained, cord fed highbay fixtures shall meet NEC 410.62(C)(1), label and listing for portable freezer units
Application received  4/15/2009 DONE
This permit was created on the web by Melissa Kaae