First Notice | 5/6/2009 | 5/6/2009 | 8/26/2010 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by Laura Longshaw
|
Final | 5/6/2009 | 5/6/2009 | 5/6/2009 | P | PASS |
Jack Frank
|
|
|
This will be for a re-inspection on the final.Please contact Ron before the inspection ###-####.he will meet you at the job site.Thanks. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok card signed
|
Final | 5/5/2009 | 5/5/2009 | 5/5/2009 | P | FAIL |
Bob Reichert
|
|
|
This will be a re-inspection for final.Contact will be Ron ###-####.Thanks and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called contractor, NEC 300.11(A) independent support wires shall be secured at both ends, 314.25 each pull or junction box shall have cover installed, 330.30(A) mc cable shallbe supporte within 12" of termination, BCC no raceways shall be supported by grid or tiles, fee due, no esc this project
|
Reinspection Fee (no hold) | 5/5/2009 | 5/5/2009 | 5/5/2009 | P | PASS |
Bob Reichert
|
|
|
This will be a re-inspection for final.Contact will be Ron ###-####.Thanks and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw see fail comments
|
Final | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | NR |
Pat Lass
|
|
|
This will be for a final inspection.Contact will be Ron ###-####.Thanks and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw box and cable to be properly supported unused openings sealed and covers on all boxes everything shall work
|
Electrical Rough-In | 4/17/2009 | 4/20/2009 | 4/20/2009 | A | PART |
Bob Reichert
|
|
|
This will be for a wall rough-in. Contact persons will be Greg or Ron. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw wall for teller line only ok to cover, no esc this project
|
Owner Supplied Equipment | | | 4/16/2009 | | |
|
|
|
|
Application received | | | 4/16/2009 | | DONE |
|
|
|
This permit was created on the web by Laura Longshaw
|