First Notice | 9/14/2009 | 9/14/2009 | 8/26/2010 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Laura Longshaw
|
Final | 9/11/2009 | 9/14/2009 | 9/14/2009 | A | PASS |
Bob Reichert
|
|
|
This is a final inspection please. Contact is Rey. Have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corrections made, ok to final, signed occupancy card, no esc this project
|
Final | 9/11/2009 | 9/11/2009 | 9/11/2009 | P | CANC |
Bob Reichert
|
|
|
This will be a final inspection please. Contact is Rey. Have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw 412 and 370 requested that morning inspection would be better due to amount of items to look at, they will recall
|
Meeting | | | 8/6/2009 | | |
|
|
|
see case notes
|
Final | 8/5/2009 | 8/5/2009 | 8/5/2009 | P | PART |
Bob Reichert
|
|
|
This inspection will be for a final please. Contact is Rey. Thank you and have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw working on corrections, need to change wiring at north light poles for green or bare grounds, repair connections- to be tight, add bell ends to u/g conduit in electrical rooms, strap emt, finish signs at panels for voltage identification, will schedule inspection for ammonia area later, told contractor owner can move in, have not signed t/o card yet, no esc this project,
|
Final | 8/5/2009 | 8/5/2009 | 8/5/2009 | A | PART |
Bob Reichert
|
|
|
look at dry goods for part final walked job with 412 and contractor, needs to add box support at outside fire valve,check listing for a/c in fire riser room, re-fuse disc for a/c, cover lb, bond piping system, in office, bond hw heater tighten all receptacles, strap mc, add fixture clip, add gfci by sink, ok to cover ceiling, add 8x8 box cover, fix dead receptacle, strap conduit, move bollards, provide work space about transformer disconnect, left correction notice NEC 110.26(A)(1),(2), (3) shall provide work space about electrical equipment- bollards and transformer disconnect
|
Electrical Rough-In | 7/29/2009 | 7/30/2009 | 7/31/2009 | A | NR |
Mike Kinnear
|
|
|
This inspection wiil be a reinspection for the ceiling that was plenum. contact is Drew White. Thank you and have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw t/w Drew mech. inspector will advise us when the return air plenum is corrected.
|
Electrical Rough-In | 7/31/2009 | 7/31/2009 | 7/31/2009 | A | PART |
Bob Reichert
|
|
|
This inspection is for over head ceiling. Rey in the contact. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok to cover ceilings in office area, no esc this project, went with 412, ceilings are changing to not being plenum depnding on structural concurrence
|
Electrical Rough-In | 7/23/2009 | 7/23/2009 | 7/23/2009 | P | FAIL |
Mike Kinnear
|
|
|
This inspection will be for a ceiling inspection. Contact is Rey. Thank you and have a wonderful day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ceiling the low voltage wiring is not plenum rated. note the high voltage wiring in the main office area is ok.
|
Electrical Rough-In | 7/23/2009 | 7/23/2009 | 7/23/2009 | P | PART |
Bob Reichert
|
|
|
hv only ok for main office ceilings, not to be covered, lv wiring not plenum rated, will call for later inspection, met and inspected with 412
|
Conference | 7/21/2009 | 7/21/2009 | 7/21/2009 | A | DONE |
Bob Reichert
|
|
|
preview final-- met 412, walked part of job to pre-final, found strapping issues, open ko, noted that ceiling is air plenum, and that low voltage wiring shall be plenum rated, violations at gear for drip shield and front clearance due to bollards too close, will go up in lift to see high bay wiring later, discussed giving ok to cover ceilings, and plug checking to final areas as requested
|
Attached Document | | | 7/21/2009 | | DONE |
|
|
|
Electric Load Test Report Attached
|
Conference | 7/2/2009 | 7/2/2009 | 7/2/2009 | A | DONE |
Bob Reichert
|
|
|
met with contractor and other electrcal inspectors to review switchgear that did not have good instructions for gounding transformer, no esc this project
|
Electrical Rough-In | 7/2/2009 | 7/2/2009 | 7/2/2009 | A | PART |
Jack Frank
|
|
|
ok met with 412,370, and Doug
|
Permanent Service | 6/4/2009 | 6/4/2009 | 6/4/2009 | P | PASS |
Mike Kinnear
|
|
|
This inspection is for all 3 p/s. Rey is contact. Thank you and have a wonderful day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw p/s u/g n ok note correction NEC310.4(A)(B)(1)thru(5) a proper load bank test on these services shall be completed prior to final sign off.
|
Permanent Service | 6/3/2009 | 6/3/2009 | 6/3/2009 | P | NR |
Jack Frank
|
|
|
This inspection will be a follow-up from yesterday for all 3 p/s. Contact is Rey. Thank you and please have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw 412 and myself met contr , not ready shall have all p/s conductors terminated at xformer, grding , bonding, ok at all 3 locations , still needs labels will check that at time of final
|
Permanent Service | 6/2/2009 | 6/2/2009 | 6/2/2009 | P | NR |
Jack Frank
|
|
|
This permit is for Main Service/switch gear. Contact is Rey. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw will do p/s 06-03-09 when all 3 p/s are ready
|
Electrical Rough-In | 6/1/2009 | 6/1/2009 | 6/1/2009 | P | PART |
Mike Kinnear
|
|
|
This inspection will be for a rough in, in wall and overhead. Contact is Rey. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok cover walls & hard lid ceilings only
|
Electrical Rough-In | 5/26/2009 | 5/26/2009 | 5/26/2009 | P | PART |
Mike Kinnear
|
|
|
This inspection will be for an in wall rough-in. Contact is Rey. Thank you and have a great day Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok cover walls only anop
|
Electrical Rough-In | 5/20/2009 | 5/20/2009 | 5/20/2009 | P | PART |
Mike Kinnear
|
|
|
This inspection will be for a partial in wall rough in. Contact is Rey. Thank you and have a wonderful day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok cover walls only anop note no esc permit in project
|
Electrical Rough-In | 5/11/2009 | 5/11/2009 | 5/12/2009 | P | PART |
Mike Kinnear
|
|
|
This will be for a rough in wall inspection. Contact is Rey Torres. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok cover walls & hard lid ceilings anop
|
Electrical Rough-In | 4/23/2009 | 4/24/2009 | 4/24/2009 | A | PART |
Mike Kinnear
|
|
|
Ray Phone #: ###-#### ok cover floor boxes main office & walls warehouse office anop
|
Application received | | | 4/23/2009 | | |
|
|
|
|
Issue permit | | | 4/23/2009 | | DONE |
|
|
|
|