First Notice | 5/12/2009 | 5/12/2009 | 10/14/2011 | | DONE |
Mike Kinnear
|
|
|
This permit finaled on the web by Therrin Robertson
|
Final | 5/11/2009 | 5/12/2009 | 5/12/2009 | A | PASS |
Mike Kinnear
|
|
|
Bank does not open till 9AM Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok final note no esc permit in project
|
Electrical Rough-In | 5/4/2009 | 5/5/2009 | 5/5/2009 | A | PASS |
Mike Kinnear
|
|
|
Ceiling Inspection Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok cover ceiling only note no esc permit in project
|
Electrical Rough-In | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | CANC |
Mike Kinnear
|
|
|
Ceiling inspection onjly Phone #: ###-#### Internet Inspection Request from: Therrin Robertson wrong type inspection
|
Conference | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | DONE |
Mike Kinnear
|
|
|
Ceiling inspection onjly Phone #: ###-#### Internet Inspection Request from: Therrin Robertson conf regarding low voltage in ceiling & supports for electrical boxes
|
Electrical Rough-In | 5/2/2009 | 5/4/2009 | 5/4/2009 | A | FAIL |
Mike Kinnear
|
|
|
Ceiling inspection request, bank does not open till 9am. Phone #: ###-#### Internet Inspection Request from: Therrin Robertson nec300.11 all wires shall be id. & attached to the grid & structual ceiling. all low voltage wiring shall not be supported by ceiling grid or any electrical equipment. note no esc permit in project
|
Electrical Rough-In | 4/25/2009 | 4/27/2009 | 4/27/2009 | A | PASS |
Mike Kinnear
|
|
|
Added partition walls supplied power to. Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok cover walls only note no esc permit in project
|
Owner Supplied Equipment | | | 4/25/2009 | | |
|
|
|
|
Application received | | | 4/25/2009 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|