Temporary Service | 5/5/2009 | 5/6/2009 | 5/6/2009 | A | PASS |
Jack Frank
|
|
|
Warren Phone #: ###-#### t/s u/g new ok
|
Temporary Service | 5/5/2009 | 5/5/2009 | 5/5/2009 | P | FAIL |
Bob Reichert
|
|
|
Warren Phone #: ###-#### called, left correction notice, NEC 250.24 grounding electrode conductor shall be connected to grounded service conductor, 312.5 shall provide abrasion protection for all conductors entering enclosure, BCC shall post job id sticker, fee due
|
Reinspection Fee (no hold) | 5/5/2009 | 5/5/2009 | 5/5/2009 | P | PASS |
Bob Reichert
|
|
|
Warren Phone #: ###-#### see fail comments, no esc this project
|
Permanent Service | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | CANC |
Bob Reichert
|
|
|
Warren Phone #: ###-#### called contractor told that this application requires temporary pole since the amount of construction could create life safety issues by converting to townhouses, no esc this project
|
Application received | | | 5/4/2009 | | |
|
|
|
|
Issue permit | | | 5/4/2009 | | DONE |