Telephone call | | | 11/10/2009 | | DONE |
Tisha Gallop
|
|
|
per telephone call with Debra Okamura/ASAP Elec. final value is $4,300//11/10/09 LEG
|
Final | 9/1/2009 | 9/1/2009 | 9/1/2009 | A | PASS |
Bob Reichert
|
|
|
corrections made, ok to final, signed occupancy card
|
Final | 8/28/2009 | 8/31/2009 | 8/31/2009 | A | FAIL |
Bob Reichert
|
|
|
Mike Phone #: ###-#### called ,left message, left correction notice, NEC 210.63 shall provide 125v, single phase 15 or 20a receptacle within 25' of hvac equipment, 210.62 shall provide showroom receptacles, 210.8(B)(5) receptacles within 6' of sink shall be gfci protected, 408.4 panel schedules shall be clear, concise and direct, 400.8 shall not use cord for substitute of fixed wiring for structure, no esc this project
|
Final | 8/28/2009 | 8/28/2009 | 8/28/2009 | P | PART |
Bob Reichert
|
|
|
Mike Phone #: ###-#### met contractor, correction notice is NEC 400.8 shall not use cords for permanent wiring of building, 408.4 shall complete circuit directory, no esc this project, will call in again
|
ELE-Aging Inspection | 8/5/2009 | 8/5/2009 | 8/11/2009 | | DONE |
Bob Reichert
|
|
|
no activity, suc
|
Application received | | | 5/6/2009 | | |
|
|
|
|
Issue & PRINT permit | | | 5/6/2009 | | DONE |
Tisha Gallop
|
|
|
|
First Notice | 9/1/2009 | 9/1/2009 | | | |
Bob Reichert
|
|
|
|