Final | 7/31/2009 | 7/31/2009 | 7/31/2009 | P | PASS |
Doug A Poedy
|
|
|
Ok final
|
Final | 7/30/2009 | 7/31/2009 | 7/31/2009 | A | NH |
Doug A Poedy
|
|
|
Steve- call for access for gate Phone #: ###-####.Called Steve left message.
|
Electrical Rough-In | 5/14/2009 | 5/14/2009 | 5/14/2009 | P | PASS |
Bob Reichert
|
|
|
Steve- call 30 mins prior to going Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 5/12/2009 | 5/12/2009 | 5/12/2009 | P | FAIL |
Jack Frank
|
|
|
Steve- Call for access Phone #: ###-#### corr met contr, 314.3 metallic fittings in plastic boxes, 314.20 outside boxes shall be flush with siding at time of r/i, 250.148 splice all equip grds together at boxes, 300.14 free length, and use approved tool for crimp sleeves, BCC and 200.6 shall not ID 6or smaller neutral to pool
|
Application received | | | 5/12/2009 | | |
|
|
|
|
Issue permit | | | 5/12/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|