Temporary Service | 6/15/2009 | 6/15/2009 | 6/15/2009 | P | PASS |
Jack Frank
|
|
|
rocky Phone #: ###-#### t/s o/h new ok
|
Temporary Service | 6/11/2009 | 6/11/2009 | 6/11/2009 | P | FAIL |
Jack Frank
|
|
|
Rocky Phone #: ###-#### see fee due for corrections
|
Reinspection Fee (no hold) | 6/11/2009 | 6/11/2009 | 6/11/2009 | P | FAIL |
Jack Frank
|
|
|
Rocky Phone #: ###-#### corr called 250.90&92 bond t/s as code noted states, 240.24(A) overcurrent device too high ,over 6ft 7", 250.64(E) use listed grding conn for GEC or use plastic, drive grd rod flush with grade, use listed fitting between service and bell box
|
Application received | | | 6/11/2009 | | |
|
|
|
|
Issue & PRINT permit | | | 6/11/2009 | | DONE |
|
|
|
|