VOIDED CHANGE STATUS | | | 7/7/2009 | | DONE |
Rita DeYoung
|
|
|
dup ele09-01120
|
Final | 6/23/2009 | 6/23/2009 | 6/23/2009 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: bill shipley called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 250.8 grounding conductors shall be terminated, 406.8 receptacles shall be listed weather resistant,590.6 shall provide gfci protection for receptacles, BCC shall post job id sticker no esc this project
|
Application received | | | 6/23/2009 | | DONE |
|
|
|
This permit was created on the web by bill shipley
|