ELE-Aging Inspection | 7/12/2010 | 7/12/2010 | 7/12/2010 | | CANC |
Jack Frank
|
|
|
|
Final | 7/12/2010 | 7/12/2010 | 7/12/2010 | P | PASS |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 5/10/2010 | 5/10/2010 | 5/13/2010 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 9/14/2009 | 9/14/2009 | 9/15/2009 | | PART |
Jack Frank
|
|
|
called contr will follow up
|
Permanent Service | 6/23/2009 | 6/24/2009 | 6/24/2009 | A | PASS |
Bob Reichert
|
|
|
Calvin Phone #: ###-#### corrections made, they will be adding door for tenant access, p/s exst meter pak rec ok, 1 meter, no esc this project
|
Permanent Service | 6/23/2009 | 6/23/2009 | 6/23/2009 | P | FAIL |
Bob Reichert
|
|
|
Calvin Phone #: ###-#### called, left correction notice, NEC 110.22 disconnects shall be labelled for its purpose, 250.8(A) grounding lug shall be connected with machine screws or at least 2 threads, 250.92(B)(4) shall use bond bushings, locknuts or other listed device at service disconnect, 110.12(A) unused openings shall be closed, 3230.72(C)each occupent shall have access to service disconnects, 225.37 shall identify all service disconnects and meters, 230.23 conductors shall have sufficient ampacity to carry the current for the load, no esc this project
|
Application received | | | 6/23/2009 | | |
|
|
|
|
Issue permit | | | 6/23/2009 | | DONE |
|
|
|
|
First Notice | 7/12/2010 | 7/12/2010 | | | |
Jack Frank
|
|
|
|