Final | 11/18/2009 | 11/18/2009 | 11/18/2009 | P | PASS |
Bob Reichert
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae met contractor, ok to final, signed occupancy card, no esc this project
|
Permanent Service | 11/2/2009 | 11/3/2009 | 11/3/2009 | P | PASS |
Jack Frank
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae p/s u/g new ok
|
Permanent Service | 10/29/2009 | 10/30/2009 | 10/29/2009 | P | CANC |
Jack Frank
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae Inspection cancelled from web by: Melissa Kaae
|
Electrical Rough-In | 9/17/2009 | 9/17/2009 | 9/17/2009 | P | PASS |
Jack Frank
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae ceiling ok
|
Electrical Rough-In | 9/14/2009 | 9/14/2009 | 9/14/2009 | P | FAIL |
Bob Reichert
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called, left correction notice, NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be secured witin 12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
|
ELE-Aging Inspection | 9/14/2009 | 9/14/2009 | 9/14/2009 | | PART |
Jack Frank
|
|
|
wsuc
|
Electrical Rough-In | 7/6/2009 | 7/6/2009 | 7/6/2009 | P | PART |
Bob Reichert
|
|
|
Contact Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Sarah Bastian u/g ok to cover anop, gave correction notice, Nec 230.2 a building or other structure shall be supplied by only 1 service- this is typical for each shelter, no esc this project
|
Application received | | | 6/23/2009 | | DONE |
|
|
|
This permit was created on the web by Melissa Kaae
|
First Notice | 11/18/2009 | 11/18/2009 | | | |
Bob Reichert
|
|
|
|