Final | 11/18/2009 | 11/18/2009 | 11/18/2009 | P | PASS |
Bob Reichert
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae ok to final,signed structural card, no esc this project
|
Permanent Service | 11/2/2009 | 11/3/2009 | 11/3/2009 | P | PASS |
Jack Frank
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae p/s u/g new ok
|
Permanent Service | 10/29/2009 | 10/30/2009 | 10/29/2009 | P | CANC |
Jack Frank
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae Inspection cancelled from web by: Melissa Kaae
|
Electrical Rough-In | 9/17/2009 | 9/17/2009 | 9/17/2009 | P | PASS |
Jack Frank
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae ceiling ok
|
Electrical Rough-In | 9/14/2009 | 9/14/2009 | 9/14/2009 | P | FAIL |
Bob Reichert
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called, left correction notice. NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be securely fastened within 12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
|
Electrical Rough-In | 7/6/2009 | 7/6/2009 | 7/6/2009 | P | PART |
Bob Reichert
|
|
|
contact Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Sarah Bastian ok to cover u/g anop, see ele09-01112 for correction notice for service to shelter, no esc this project
|
Application received | | | 6/23/2009 | | DONE |
|
|
|
This permit was created on the web by Melissa Kaae
|
First Notice | 11/18/2009 | 11/18/2009 | | | |
Bob Reichert
|
|
|
|