Final | 9/16/2009 | 9/17/2009 | 9/17/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dave Friend ok to final, no esc this project
|
Final | 8/27/2009 | 8/28/2009 | 8/28/2009 | A | NR |
Jack Frank
|
|
|
Bob Phone #: ###-#### no power too shed called
|
Final | 7/13/2009 | 7/14/2009 | 7/14/2009 | A | CANC |
Bob Reichert
|
|
|
Please cal ###-#### to confirm final inspection has passed. Phone #: ###-#### Internet Inspection Request from: Dave Friend called, wrong type request, see rip
|
Rough-In Permanent Service | 7/14/2009 | 7/14/2009 | 7/14/2009 | A | PASS |
Bob Reichert
|
|
|
Please cal ###-#### to confirm final inspection has passed. Phone #: ###-#### Internet Inspection Request from: Dave Friend called, corrections made, ri ok, u/g ok to cover, p/s o/h n ok, no esc thisproject
|
Final | 7/7/2009 | 7/7/2009 | 7/7/2009 | P | FAIL |
Doug A Poedy
|
|
|
Shed sits behind house. You may go behind house and do not need to contact the residence since it is a rental. Phone #: ###-#### Internet Inspection Request from: Dave Friend. Correction notice posted. NEC 110.12 Unused openings shall be closed,NEC 344.46 Where a conduit enters a box a bushing shall be provided for abrasion protection.NEC 334.15(B) Exposed NM cable shall be protected from physical damage,NEC 210.4(B) Multiwire branch circuits shall disconnect simultaneously,NEC 300.5 direct buried conduit shall be installed to meet the minimum cover requirements of table 300.5.
|
Application received | | | 7/7/2009 | | DONE |
|
|
|
This permit was created on the web by Dave Friend
|