ELE-Aging Inspection | 9/16/2009 | 9/16/2009 | 9/16/2009 | | CANC |
Jack Frank
|
|
|
|
Final | 9/16/2009 | 9/16/2009 | 9/16/2009 | P | PASS |
Jack Frank
|
|
|
|
Temporary Service | 7/8/2009 | 7/8/2009 | 7/8/2009 | P | FAIL |
Bob Reichert
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae met contractor, told could not hook up trailer with cord since trailer not portable or listed, gave partial correction notice for trailer,Nec 400.5(A) soow cord rated at 45A, 408.4 shall provide circuit directory, 240.81 breaker handles shall be on in up position, 400.8 shall not use so cord for substitution of fixed wiring, left correction notice for temporary pole NEC 406.8 15 and 20a receptacles shall be listed weather resistant, 406.4 receptacle shall have faceplate installed, 110.9 shall provide equipment rated for available fault current, no esc this project
|
Application received | | | 7/7/2009 | | DONE |
|
|
|
This permit was created on the web by Melissa Kaae
|
First Notice | 9/16/2009 | 9/16/2009 | | | |
Jack Frank
|
|
|
|