Final | 8/6/2009 | 8/6/2009 | 8/6/2009 | P | PASS |
Jack Frank
|
|
|
Dave Phone #: ###-#### ok
|
Final | 8/3/2009 | 8/3/2009 | 8/3/2009 | P | NR |
Jack Frank
|
|
|
Please Call me before inspection. And i will meet you there. Thanks Dave Phone #: ###-#### Internet Inspection Request from: jason shifflett called needs disconnect for out blding
|
Electrical Rough-In | 7/16/2009 | 7/16/2009 | 7/16/2009 | A | PASS |
Bob Reichert
|
|
|
dave-###-#### corrections made, ric ok, u/g house to garage ok to cover, single 15a gfci circuit to garage, 1" sleeve for future phone
|
Electrical Rough-In | 7/14/2009 | 7/15/2009 | 7/15/2009 | A | FAIL |
Bob Reichert
|
|
|
Internet Inspection Request from: jason shifflett no number left, called numbers, no response, bad contacts till they call in number, left correction notice,NEC 250.52(A)(3) shall provide concrete encased electrode, 230.66 service equipment shall be marked to identify as being suitable for use as service equipment, 110.12(A) unused openings shall be closed, 314.27)A) shall supply boxes for luminaires, Note: no underground seen
|
Application received | | | 7/14/2009 | | DONE |
|
|
|
This permit was created on the web by jason shifflett
|