Permanent Service | 7/31/2009 | 7/31/2009 | 7/31/2009 | P | PASS |
Jack Frank
|
|
|
Dave Phone #: ###-#### p/s o/h rec. ok
|
Final | 7/31/2009 | 7/31/2009 | 7/31/2009 | P | PASS |
Jack Frank
|
|
|
Dave Phone #: ###-####
|
Permanent Service | 7/29/2009 | 7/29/2009 | 7/29/2009 | P | FAIL |
Jack Frank
|
|
|
dave Phone #: ###-#### c alled all violations not corrected GEC shall terminate at neutral bus,
|
Permanent Service | 7/28/2009 | 7/28/2009 | 7/28/2009 | P | FAIL |
Jack Frank
|
|
|
Dave Phone #: ###-#### called corr 250.24(A)(1) & 200.2(B) terminate GEC and all neutrals to neutral bus, 230.28 install guy kit above couplings on mast, 110.12(A) needs KO seals, 300.10&12 use 2 locknuts for rigid nipple entering p/s, also needs bushing 344.46, 250.52(A)(1) terminate GEC within 5 ft of where u/g water enters bld, note make sure meterbase is 150 amp rated
|
Reinspection Fee (no hold) | 7/28/2009 | 7/28/2009 | 7/28/2009 | P | PASS |
Jack Frank
|
|
|
Dave Phone #: ###-#### corr fee due
|
Permanent Service | 7/27/2009 | 7/27/2009 | 7/27/2009 | P | PART |
Jack Frank
|
|
|
Dave-late afternoon please Phone #: ###-#### ok for late ID Po rec. contr will call for inspection tuesday AM
|
Application received | | | 7/20/2009 | | |
|
|
|
|
Issue permit | | | 7/20/2009 | | DONE |
|
|
|
|