First Notice | 7/24/2009 | 7/24/2009 | 6/13/2016 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by Spencer McLean
|
Temporary Service | 7/23/2009 | 7/24/2009 | 7/24/2009 | A | PASS |
Jack Frank
|
|
|
Please provide temp power pole inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean t/s u/g new ok
|
Temporary Service | 7/21/2009 | 7/22/2009 | 7/22/2009 | A | FAIL |
Bob Reichert
|
|
|
Please provide termpory power pole inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean met electrician, gave correction notice, NEC 406.8(B)(1) receptacles shall be rated weather resistant, 310.16 shall provide minimum 100A use type service conductors, BCC shall provide job id stickers, fee due, no esc this project
|
Reinspection Fee (no hold) | 7/22/2009 | 7/22/2009 | 7/22/2009 | A | PASS |
Bob Reichert
|
|
|
Please provide termpory power pole inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean see fail response
|
Application received | | | 7/21/2009 | | DONE |
|
|
|
This permit was created on the web by Spencer Mclean
|