Final | 2/3/2010 | 2/4/2010 | 2/4/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren ok to final
|
Electrical Rough-In | 9/24/2009 | 9/25/2009 | 9/25/2009 | P | PART |
Doug A Poedy
|
|
|
Electrical rough inspection in the basement Phone #: ###-#### Internet Inspection Request from: Stephen Kren. ok to cover downstairs and stairwell.
|
Rough-In Permanent Service | 9/10/2009 | 9/11/2009 | 9/11/2009 | A | FAIL |
Bob Reichert
|
|
|
the unfinished basement is ready for a rough inspection, thx, TW. Phone #: ###-#### Internet Inspection Request from: Stephen Kren called, NOTE: partial inspection only, BCC shall not cover wiring before cover, NEC 400.8 shall not use flexible cord as a substitute for fixed wiring of structure, 300.14 at least 6" free conductor length shall be left at each box, 110.12 there shall be no damaged parts (mc cable), fee due
|
Reinspection Fee (no hold) | 9/11/2009 | 9/11/2009 | 9/11/2009 | A | PASS |
Bob Reichert
|
|
|
the unfinished basement is ready for a rough inspection, thx, TW. Phone #: ###-#### Internet Inspection Request from: Stephen Kren see fail inspection
|
Rough-In Permanent Service | 9/9/2009 | 9/10/2009 | 9/10/2009 | A | CANC |
Bob Reichert
|
|
|
Rough in inspection needed for the basement only, any questions please call, thx, Terry. Phone #: ###-#### Internet Inspection Request from: Stephen Kren called, contractor asked to cancel
|
Permanent Service | 7/27/2009 | 7/27/2009 | 7/27/2009 | P | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 7/24/2009 | 7/27/2009 | 7/27/2009 | P | PART |
Bob Reichert
|
|
|
inspection needed for approval to cover on the upstairs of the home only, thx. Phone #: ###-#### Internet Inspection Request from: Stephen Kren main floor level only ok to cover, told electrician to change room count on permit - there are about 21 rooms on main floor, but the basement needs finished to get a total count
|
Application received | | | 7/24/2009 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|