Permit Information
Permit NumberELE09-01512
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 1417 W JEFFERSON ST
Project Name 
Customer Number09-009
ePlanReview 
Description
Electrical Permit - Addition: Electrical wiring for new Transient Women''s Dormitory. Includes new building multi-metering switchgear, lighting, outlets and HVAC connections.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/16/200911/17/200911/17/2009APASS
DetailsBob Reichert
steve Phone #: ###-#### ok to final, no card to sign
Permanent Service10/29/200910/29/200910/29/2009PPASS
DetailsDoug A Poedy
Doug/Bob, We are changing out the service on the Boise Rescue Misson Dorm today. Idaho Power is shutting off at 9am. We hope to be complete by 2pm. Please arrive at 1pm if possible. This is a critical change as the service feeds 8 apartments. We have to get it heated up asap! Thanks, Steve Harris ###-#### or Loren Ramsey ###-#### Phone #: ###-#### Internet Inspection Request from: Loren Ramsey. P/S U/G Reconnect ok.
Electrical Rough-In10/8/200910/9/200910/9/2009APASS
DetailsDoug A Poedy
steve Phone #: ###-####. Ok to cover.
Electrical Rough-In9/30/200910/1/200910/1/2009APART
DetailsDoug A Poedy
Steve Phone #: ###-####. ok to cover except for electrical room, riser room, and mech. room.
Electrical Rough-In8/27/20098/27/20098/27/2009PPART
DetailsDoug A Poedy
Steve Phone #: ###-####. Ok to cover underground conduit for street lighting.
Electrical Rough-In8/26/20098/26/20098/26/2009PPART
DetailsDoug A Poedy
Steve Phone #: ###-####. Ok to cover driveway section of underground conduit.
Conference8/25/20098/26/20098/26/2009PDONE
DetailsDoug A Poedy
Steve Phone #: ###-####
Electrical Rough-In8/24/20098/25/20098/25/2009APASS
DetailsDoug A Poedy
Steve-Underground upher inspection please Phone #: ###-####. Concrete encased electrode looks gtood. Ok to cover.
Electrical Rough-In8/19/20098/20/20098/20/2009APASS
DetailsDoug A Poedy
steve - undergruond Phone #: ###-####. Ok to cover concrete encased electrode with 2 inches of concrete.
Electrical Rough-In8/19/20098/19/20098/19/2009PFAIL
DetailsDoug A Poedy
Steve Harris-underground inspection please Phone #: ###-####. NEC 250.52 3 Concrete encased electrode needs to be on footing.
Application received  8/18/2009 DONE
This permit was created on the web by Kevin Perez
First Notice11/17/200911/17/2009   
DetailsBob Reichert