Electrical Rough-In | 9/2/2009 | 9/2/2009 | 9/2/2009 | P | PASS |
Jack Frank
|
|
|
Requesting a inspection of 5 new roof top units. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok corr made
|
Final | 9/2/2009 | 9/2/2009 | 9/2/2009 | A | PASS |
Jack Frank
|
|
|
Requesting a inspection of 5 new roof top units. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty
|
Electrical Rough-In | 9/1/2009 | 9/1/2009 | 9/1/2009 | P | FAIL |
Jack Frank
|
|
|
called corr. 314.28 angle pulls for 4 and larger, 300.4(G) bushings for 4 and larger,110.3(A) replace damaged conductor at terminals wire ringed
|
Electrical Rough-In | 8/31/2009 | 9/1/2009 | 9/1/2009 | A | NH |
Jack Frank
|
|
|
Requesting inspection of 5 new rooftop units. Please call before to meet with Skip, ###-####. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty see added p/m request
|
Owner Supplied Equipment | | | 8/20/2009 | | |
|
|
|
|
Application received | | | 8/20/2009 | | DONE |
|
|
|
This permit was created on the web by Dan Hardisty
|
First Notice | 9/2/2009 | 9/2/2009 | | | |
Jack Frank
|
|
|
|