Temporary Service | 8/25/2009 | 8/26/2009 | 8/26/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made, t/s u/g n ok
|
Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 | A | FAIL |
Bob Reichert
|
|
|
Brandon Phone #: ###-#### called, left correction notice NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
|
Application received | | | 8/24/2009 | | |
|
|
|
|
Issue permit | | | 8/24/2009 | | DONE |
|
|
|
|
Reinspection Fee (no hold) | 8/25/2009 | 8/25/2009 | | P | |
Bob Reichert
|
|
|
|