First Notice | 9/29/2009 | 9/29/2009 | 8/5/2010 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/28/2009 | 9/29/2009 | 9/29/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: John VanZandt ok to final, no card to sign, people moved in, did check receptacles on walls
|
Permanent Service | 9/21/2009 | 9/21/2009 | 9/21/2009 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/21/2009 at 10:59:37 AM. Contact: ###-####. ok to backfill gec, p/s o/h n ok
|
Electrical Rough-In | 9/9/2009 | 9/9/2009 | 9/9/2009 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/9/2009 at 10:02:36 AM. Contact: ###-####. corrections made, ric ok, ok to pour concrete encased electrode
|
Rough-In Permanent Service | 9/9/2009 | 9/9/2009 | 9/9/2009 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/9/2009 at 10:02:36 AM. Contact: ###-####. wrong type request, see ri
|
Rough-In Permanent Service | 9/8/2009 | 9/9/2009 | 9/9/2009 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/8/2009 at 3:13:35 PM. Contact: ###-####. called, left correction notice, NEC 300.14 at least 6" free conductor shall be left at each point where it emerges from raceway for splice, 300.4 shall provide steel plate where bored hole is less than 1 1/4" from edge of framing member, 250.52(A)(3) concrete encased electrode shall have 2" concrete encasement, 230, shall provide service clearance for existing building
|
Application received | | | 9/8/2009 | | |
|
|
|
|
Issue & PRINT permit | | | 9/8/2009 | | DONE |
|
|
|
|