Final | 10/22/2009 | 10/22/2009 | 10/22/2009 | P | PASS |
Jack Frank
|
|
|
daniel - call for access Phone #: ###-#### ok
|
Final | 10/21/2009 | 10/21/2009 | 10/21/2009 | P | FAIL |
Bob Reichert
|
|
|
Daniel Phone #: ###-#### called, left correction notice, NEC 200.7 shall not use white for phase conductor at a/c, 406.4 shall securely mount receptacles, 422.11(A) shall not exceed rating of a/c nameplate for overcurrent protection, 210.52(C)(2)(4) shall add receptacle to left of sink in countertop space
|
Electrical Rough-In | 9/9/2009 | 9/10/2009 | 9/10/2009 | A | CANC |
Jack Frank
|
|
|
daniel Phone #: ###-#### see added r/i p/s
|
Rough-In Permanent Service | 9/10/2009 | 9/10/2009 | 9/10/2009 | P | PASS |
Jack Frank
|
|
|
daniel Phone #: ###-#### r/i p/s u/g new ok
|
Application received | | | 9/9/2009 | | |
|
|
|
|
Issue permit | | | 9/9/2009 | | DONE |
|
|
|
|