First Notice | 10/5/2009 | 10/5/2009 | 8/4/2015 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by April Brown
|
Temporary Service | 10/2/2009 | 10/5/2009 | 10/5/2009 | A | PASS |
Bob Reichert
|
|
|
Please meet me at the job site at 8:30 am on oct 5.Thanks Bruce Phone #: ###-#### Internet Inspection Request from: Bruce Herold corrections made, t/s u/g n ok, no esc this project
|
Final | 10/1/2009 | 10/2/2009 | 10/2/2009 | A | CANC |
Bob Reichert
|
|
|
please call 1 hour before inspection to allow me to meet you at the site and gain access. thanks,Bruce Phone #: ###-#### Internet Inspection Request from: Bruce Herold contractor called, cannot get access to trailer, will call for inspection later
|
Final | 9/24/2009 | 9/25/2009 | 9/25/2009 | A | FAIL |
Jack Frank
|
|
|
call Stan for access ###-#### Phone #: ###-#### Internet Inspection Request from: Bruce Herold corr called clean t/s 110.12(B) 110.3(B) feeder to job trailer shall be sized to trailer nameplate, T400.5(A) size co cord for amps, provide access to site, call for a t/s inspection 110.9&10 gear shall be rated for fault and short circuit currentwhen next to xformer
|
Reinspection Fee (no hold) | 9/25/2009 | 9/25/2009 | 9/25/2009 | A | PASS |
Jack Frank
|
|
|
call Stan for access ###-#### Phone #: ###-#### Internet Inspection Request from: Bruce Herold fee due corr. no access
|
Application received | | | 9/24/2009 | | DONE |
|
|
|
This permit was created on the web by Bruce Herold
|