First Notice | 4/9/2010 | 4/9/2010 | 8/23/2010 | | DONE |
Doug A Poedy
|
|
|
This permit finaled on the web by Scott Campbell
|
First Notice | 4/9/2010 | 4/9/2010 | 8/23/2010 | | DONE |
Doug A Poedy
|
|
|
This permit finaled on the web by Scott Campbell
|
Final | 4/9/2010 | 4/9/2010 | 4/9/2010 | P | PASS |
Doug A Poedy
|
|
|
Inspection requested from web by: Scott Campbell Phone #: ###-####
|
DOC - Permit Finaled | 4/9/2010 | 4/9/2010 | 4/9/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 4/7/2010 | 4/8/2010 | 4/8/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Scott Campbell Phone #: ###-#### called, left correction notice, NEC 230.2)E), 225.37 shall identify services, 406.8 shall install listed wr type receptacles and in-use covers for outdoor receptacles, 210.8(B)(5) receptacles within 6' of sink shall be gfci protected, 406.4 receptacles shall be securely mounted, 406.4(D) receptacle face shall be flush with or project from faceplate NOTE: corrections shall be made within 5 working days or further action will be taken such as removal of power
|
Electrical Rough-In | 3/18/2010 | 3/19/2010 | 3/19/2010 | A | PART |
Bob Reichert
|
|
|
For Temporary Occupancy - New Shed Inspection requested from web by: Scott Campbell Phone #: ###-#### t/o ok for 4.4A, 5, & 6 only, signed card with correction to affix service disconnect stickers to each service
|
Electrical Rough-In | 1/19/2010 | 1/19/2010 | 1/19/2010 | P | PASS |
Bob Reichert
|
|
|
Steve Phone #: ###-#### called, corrections made, ric ok
|
Electrical Rough-In | 1/13/2010 | 1/14/2010 | 1/14/2010 | P | FAIL |
Bob Reichert
|
|
|
Contact is John Dillon Phone #: ###-#### Internet Inspection Request from: Scott Campbell called contractor, left correction notice, NEC 225.36 disconnecting means shall be suitable for service equipment at each building, 348.30,330.30 fmc and mc shall be securely supported within 12" of box, 250.86 shall ground metal boxes,300.4(A)&(D) edge of bored holes and mc cables shall be 1 1/4" from edge of framing member,250.32 shall provide disconnecting means inside or outside of building served per 225.31, 250.32(B) grounded conductor shall not connect to equipment grounding conductor, 110.12(A) shall close unused openings
|
Final | 12/10/2009 | 12/11/2009 | 12/11/2009 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Campbell part final ok, called contractror to tighten receptacles, provide gfci for drinking fountains and refrigerator, signed t/o card
|
Electrical Rough-In | 11/20/2009 | 11/20/2009 | 11/20/2009 | P | PASS |
Bob Reichert
|
|
|
Contact: John Dillon Phone #: ###-#### Internet Inspection Request from: Randy Vail pole bases ok to pour
|
Electrical Rough-In | 11/9/2009 | 11/9/2009 | 11/9/2009 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
|
Electrical Rough-In | 11/6/2009 | 11/6/2009 | 11/6/2009 | P | PART |
Bob Reichert
|
|
|
Cover Inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail u/g ok 2nd building to east of main building mark plans next inspection, electrician not on site with plans
|
Electrical Rough-In | 11/4/2009 | 11/4/2009 | 11/4/2009 | P | PART |
Bob Reichert
|
|
|
u/g ok to cover anop
|
Electrical Rough-In | 11/3/2009 | 11/4/2009 | 11/4/2009 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail
|
Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
|
Electrical Rough-In | 10/28/2009 | 10/28/2009 | 10/28/2009 | P | PART |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok cover under ground conduct anop
|
Electrical Rough-In | 10/26/2009 | 10/27/2009 | 10/27/2009 | A | PART |
Bob Reichert
|
|
|
underground inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail u/g ok to cover anop
|
Electrical Rough-In | 10/26/2009 | 10/26/2009 | 10/26/2009 | P | CANC |
Bob Reichert
|
|
|
Underground inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail Inspection cancelled from web by: Randy Vail
|
Final | 10/22/2009 | 10/23/2009 | 10/23/2009 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail wrong type request, see ri
|
Electrical Rough-In | 10/23/2009 | 10/23/2009 | 10/23/2009 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
|
Electrical Rough-In | 10/21/2009 | 10/22/2009 | 10/22/2009 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop, told to provide service at each building along with electrodes
|
Electrical Rough-In | 10/14/2009 | 10/15/2009 | 10/15/2009 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail offices only ok to cover
|
Permanent Service | 9/29/2009 | 9/30/2009 | 9/30/2009 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/29/2009 at 12:34:34 PM. Contact: ###-####. p/s u/g n ok
|
Application received | | | 9/25/2009 | | DONE |
|
|
|
This permit was created on the web by Randy Vail
|