Temporary Service | 11/4/2009 | 11/5/2009 | 11/5/2009 | A | PASS |
Bob Reichert
|
|
|
Brett Phone #: ###-#### corrections made, t/s o/h n ok
|
Temporary Service | 10/29/2009 | 10/30/2009 | 10/30/2009 | A | FAIL |
Bob Reichert
|
|
|
Bret ###-#### called, left correction notice, NEC 312.5 shall provide abrasion protection for all conductors entering enclosure, 250.28 shall provide main bonding jumper, 250.92 shall provide raceway bonding at service, 406.8(B) 120v receptacles shall be listed weather resistant type, 408.4 shall provide clear and correct and concise circuit directory, 334.12 shall not use nm cable in wet or damp locations, 230.41 service conductors shall be insulated
|
Application received | | | 10/29/2009 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/29/2009 | | DONE |
|
|
|
|