Final | 12/7/2009 | 12/8/2009 | 12/8/2009 | A | PASS |
Bob Reichert
|
|
|
Please call 30 mins prior to inspection-Gary Phone #: ###-#### ok to final, no esc this project
|
Electrical Rough-In | 11/19/2009 | 11/20/2009 | 11/20/2009 | A | PASS |
Bob Reichert
|
|
|
Gary Phone #: ###-#### corrections made, ric ok, no esc this project
|
Electrical Rough-In | 11/19/2009 | 11/19/2009 | 11/19/2009 | P | FAIL |
Bob Reichert
|
|
|
Gary will not be home until 3:30 please call before going out THANKS Phone #: ###-#### called, could only do outside, left correction notice, NEC 314.20 in walls of combustible material, boxes shall be flush with or project from finished surface, told owner appointment needs to be done 1st thing in pm if he wants pm inspection
|
Conference | 11/5/2009 | 11/6/2009 | 11/6/2009 | P | DONE |
Bob Reichert
|
|
|
after 3pm please (gets off of work at 2:30)//Gary ###-#### talked with owner, suggested that he get book on wiring, reviewed what inspector will look for, told him inspector can't do design, went over free length of conductor, make-up, box sizes, 1 1/4", circuit additions, breakers to be per manufacturer instruction, pocket doors, 6'-12' receptacle spacing, can lights, no esc this project
|
Issue PAID IN FULL permit | | | 11/5/2009 | | DONE |
|
|
|
|
Application received | | | 11/5/2009 | | |
|
|
|
|