Final | 1/19/2010 | 1/19/2010 | 1/19/2010 | P | PASS |
Bob Reichert
|
|
|
READY AFTER 12.00 Phone #: ###-#### Internet Inspection Request from: Bob Glenn ok to final
|
Rough-In Permanent Service | 11/20/2009 | 11/23/2009 | 11/23/2009 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn wrong type request, see ri
|
Electrical Rough-In | 11/23/2009 | 11/23/2009 | 11/23/2009 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn corrections made, ric ok
|
Electrical Rough-In | 11/20/2009 | 11/20/2009 | 11/20/2009 | A | FAIL |
Bob Reichert
|
|
|
called, left correction notice, NEC 300.14 shall provide at least 6" free conductor at boxes- garage, 210.52(A)(1) receptacles shall be spaced such that no point is over 6' from an outlet-entry, front left room, upper landing,upper room, 110.12(B) there shall be no broken boxes-master bath, media room, 110.3(B) listed equipment shall be installed per instructions included with listed product-jetted tub, BCC shall add 5 rooms to permit
|
Permanent Service | 11/20/2009 | 11/20/2009 | 11/20/2009 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Rough-In Permanent Service | 11/19/2009 | 11/20/2009 | 11/20/2009 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called, see ri and p/s
|
Application received | | | 11/19/2009 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|