Final | 12/1/2009 | 12/2/2009 | 12/2/2009 | A | PASS |
Bob Reichert
|
|
|
robert Phone #: ###-#### ok to final, no esc this project
|
Permanent Service | 12/2/2009 | 12/2/2009 | 12/2/2009 | A | PASS |
Bob Reichert
|
|
|
robert Phone #: ###-#### corrections made, p/s o/h n ok, no esc this project
|
Permanent Service | 11/30/2009 | 11/30/2009 | 11/30/2009 | P | FAIL |
Bob Reichert
|
|
|
Robert Phone #: ###-#### called, left correction notice, NEC 312.5, 550.10(B) all conductors entering enclosure shall have abrasion protection, 240.5 ampacity of cord and receptacle shall be protected per table 400.5, 550.10(D) cord length shall be betwee 21' and 361/2', 550.10(G) cord shall be protected thru wall and floor, 110.12(A) shall close openings in mast weatherhead,110.3(A) ,110.20 outdoor enclosure shall be weather proof, 110.13 equipment shall be securely mounted and connections properly installed- cord connectors, no esc this project
|
Application received | | | 11/30/2009 | | |
|
|
|
|
Issue permit | | | 11/30/2009 | | DONE |
|
|
|
|