Final | 6/14/2010 | 6/15/2010 | 6/15/2010 | A | PASS |
Jack Frank
|
|
|
House is open. garage code is 1418 Inspection requested from web by: Joe Thomas Phone #: ###-####
|
Electrical Rough-In | 5/25/2010 | 5/26/2010 | 5/26/2010 | A | PASS |
Doug A Poedy
|
|
|
Request for approval to cover trench for underground wire from house to garage. Located on North side of house. UF wire is GFCI protected. Inspection requested from web by: Joe Thomas Phone #: ###-####
|
Electrical Rough-In | 1/7/2010 | 1/8/2010 | 1/8/2010 | A | PASS |
Jack Frank
|
|
|
Front door is unlocked. House is vacant. Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok check clearence MB closet fixture at final
|
Rough-In Permanent Service | 12/18/2009 | 12/18/2009 | 12/18/2009 | P | PASS |
Doug A Poedy
|
|
|
Permanent service inspection. Fixeed ground wire correction and removed ser from conduit. We will make corrections on SER later. Just need meter main inspection for Idaho power swing. House is unlocked nobody lives there. Phone #: ###-#### Internet Inspection Request from: Joe Thomas. P/S O/H Reconnect ok.
|
Permanent Service | 12/17/2009 | 12/18/2009 | 12/18/2009 | A | FAIL |
Jack Frank
|
|
|
New permanent service inspection. For Idaho power swing. Existing service and all existing wiring in house will be gone after power is switched over. Sunroom on back of house is to be demolished. Incoming water pipe is plastic. Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr. called needs listed or plastic conn. for GEC 312.5(C) exception ser cable not allowed in conduit out the bottom of panel, no access to inside of house
|
Application received | | | 12/16/2009 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|