Rough-In Permanent Service | 12/22/2009 | 12/22/2009 | 12/22/2009 | P | PASS |
Jack Frank
|
|
|
Dan Phone #: ###-#### p/s u/g rec ok
|
Final | 12/22/2009 | 12/22/2009 | 12/22/2009 | P | PASS |
Jack Frank
|
|
|
Dan Phone #: ###-#### needs plastic conn for GEC , also terminate GEC at p/s not jbox, shall not re ID 6 or smaller neutral
|
Permanent Service | 12/16/2009 | 12/18/2009 | 12/18/2009 | P | FAIL |
Jack Frank
|
|
|
dan Phone #: ###-#### met contr, correction posted art. 220 shall calc p/s for correct size needs 200 amp ?, 240.24 (D) panel not allowed in clothes closet
|
Application received | | | 12/16/2009 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/16/2009 | | DONE |
|
|
|
|