Final | 4/23/2010 | 4/23/2010 | 4/23/2010 | P | PASS |
Doug A Poedy
|
|
|
Steve Phone #: ###-####
|
DOC - Permit Finaled | 4/23/2010 | 4/23/2010 | 4/23/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Electrical Rough-In | 1/19/2010 | 1/19/2010 | 1/19/2010 | P | PASS |
Bob Reichert
|
|
|
Steve Phone #: ###-#### corrections made, called about recpt in 2nd floor room by lv cables and smoke detector, left message, ric ok
|
ELE-Aging Inspection | 1/14/2010 | 1/14/2010 | 1/14/2010 | P | DONE |
Bob Reichert
|
|
|
status check for correction notice
|
Rough-In Permanent Service | 1/11/2010 | 1/11/2010 | 1/11/2010 | P | CANC |
Bob Reichert
|
|
|
Steve Phone #: ###-#### wrong type request see p/s
|
Permanent Service | 1/11/2010 | 1/11/2010 | 1/11/2010 | P | PASS |
Bob Reichert
|
|
|
Steve Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 1/11/2010 | 1/11/2010 | 1/11/2010 | P | FAIL |
Bob Reichert
|
|
|
Steve Phone #: ###-#### called, left message, left correction notice,NEC 300.4 edge of bored holes shall be 1 1/4" from edge of framing members or cable shall be protected be steel plates, 210.52(A) shall install receptacles such that no point along wall line is over 6' from an outlet, NOTE : shall affix box in kitchen, terminate nm cable in kitchen ceiling, adress either 3rd floor unfinished or not
|
Application received | | | 1/11/2010 | | |
|
|
|
|
Issue permit | | | 1/11/2010 | | DONE |
|
|
|
|