First Notice | 3/3/2010 | 3/3/2010 | 2/14/2011 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 3/2/2010 | 3/3/2010 | 3/3/2010 | A | PASS |
Bob Reichert
|
|
|
Contact Paul Cushing Inspection requested from web by: Shelli Daylong Phone #: ###-#### corrections made, ok to final, no esc this project
|
Final | 2/24/2010 | 2/24/2010 | 2/24/2010 | P | FAIL |
Bob Reichert
|
|
|
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### called, left correction notice, NEC 210.70(C) shall provide switched lighting outlet in pump hpuse, 110.22(A) shall identify disconnecting means with sufficient durability to withstand environment, 408.4 shall provide circuit directories, NOTE corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 2/24/2010 | 2/24/2010 | 2/24/2010 | P | PASS |
Bob Reichert
|
|
|
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to cover u/g to sign only
|
Final | 1/25/2010 | 1/25/2010 | 1/25/2010 | P | CANC |
Doug A Poedy
|
|
|
Contact: Paul Cushing before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden
|
Application received | | | 1/12/2010 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|