Permit Information
Permit NumberELE10-00062
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 2350 W HILL RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Repair existing PVC conduit to meet code. Install (2) 100-amp subpanels to accommodate new Greenhouse, connect power to existing sign power and install ground wire to existing subpanel
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice3/3/20103/3/20102/14/2011 DONE
DetailsBob Reichert
This permit finaled on the web by Deb Gooden
Final3/2/20103/3/20103/3/2010APASS
DetailsBob Reichert
Contact Paul Cushing Inspection requested from web by: Shelli Daylong Phone #: ###-#### corrections made, ok to final, no esc this project
Final2/24/20102/24/20102/24/2010PFAIL
DetailsBob Reichert
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### called, left correction notice, NEC 210.70(C) shall provide switched lighting outlet in pump hpuse, 110.22(A) shall identify disconnecting means with sufficient durability to withstand environment, 408.4 shall provide circuit directories, NOTE corrections shall be made within 5 working days or further action will be taken
Electrical Rough-In2/24/20102/24/20102/24/2010PPASS
DetailsBob Reichert
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to cover u/g to sign only
Final1/25/20101/25/20101/25/2010PCANC
DetailsDoug A Poedy
Contact: Paul Cushing before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden
Application received  1/12/2010 DONE
This permit was created on the web by Deb Gooden