Final | 4/29/2010 | 4/30/2010 | 4/30/2010 | A | PASS |
Bob Reichert
|
|
|
chris Phone #: ###-#### ok to final, receptacle installed
|
Final | 4/29/2010 | 4/29/2010 | 4/29/2010 | P | PASS |
Doug A Poedy
|
|
|
Verbal survey-needs outlet in dining room per 210.52 A2. will verify on 4-30-10
|
Conference | 4/28/2010 | 4/28/2010 | 4/28/2010 | A | DONE |
Doug A Poedy
|
|
|
Correction notice is correct. Corrections shall be made before final.
|
Final | 4/26/2010 | 4/27/2010 | 4/27/2010 | P | PART |
Bob Reichert
|
|
|
Inspection requested from web by: Justin Frates corrections not made, had owner call 414 to confirm need for convenience outlet, tub opening not ready, will need to call for final when done
|
Final | 4/26/2010 | 4/26/2010 | 4/26/2010 | P | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Justin Frates called, left correction notice, NEC 210.52(A)(2) shall provide receptacle under bar/counter, 406.4 all receptacles shall be securely mounted, 406.4(D) receptacle face shall be flush with or project from cover, 406.5 receptacle covers shall be installed, 110.3 receptacles in laundry room shall operate, shall provide 12"x34" access in tub for maintenance, 410.2 shall provide clearance for closet fixture- purple room, BCC shall install trim for fixtures over desk, NOTE corrections shall be made within 5 working days or further action will be taken such as removal of power
|
Final | 4/23/2010 | 4/26/2010 | 4/26/2010 | A | NH |
Bob Reichert
|
|
|
The tub upstairs will have a caulked removable tile to access the pump. Inspection requested from web by: Justin Frates Phone #: ###-#### called, nh, told to reschedule, fee due, left card
|
Reinspection Fee (no hold) | 4/26/2010 | 4/26/2010 | 4/26/2010 | P | PASS |
Bob Reichert
|
|
|
The tub upstairs will have a caulked removable tile to access the pump. Inspection requested from web by: Justin Frates Phone #: ###-#### see nh
|
Electrical Rough-In | 1/22/2010 | 1/25/2010 | 1/25/2010 | A | PASS |
Bob Reichert
|
|
|
Justin Phone #: ###-#### corrections made, ric ok
|
Rough-In Permanent Service | 1/21/2010 | 1/22/2010 | 1/22/2010 | A | CANC |
Bob Reichert
|
|
|
Justin Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 1/22/2010 | 1/22/2010 | 1/22/2010 | A | FAIL |
Bob Reichert
|
|
|
Justin Phone #: ###-#### called, left message, left correction notice, NEC 334.30 shall secure nm cable within 12" of box, 210.52(A)(1) shall install receptacles such that no point along floor line is over 6' from an outlet- south entry room, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 110.12(B) there shall be no broken boxes-north part kitchen, 110.3(B) shall install listed equipment in accordance with instructions i.e. shall ensure that access to jetted tub is provide with 12"x24" opening, BCC shall provide boxes for under stair light, range, 240v circuit in basement
|
Permanent Service | 1/22/2010 | 1/22/2010 | 1/22/2010 | A | PASS |
Bob Reichert
|
|
|
Justin Phone #: ###-#### p/s u/g n ok
|
Application received | | | 1/21/2010 | | |
|
|
|
|
Issue permit | | | 1/21/2010 | | DONE |
Barbara Stitt
|
|
|
|