Final | 2/24/2010 | 2/24/2010 | 2/24/2010 | P | PASS |
Bob Reichert
|
|
|
keith Phone #: ###-#### ok to final, no esc this project
|
Rough-In Permanent Service | 1/26/2010 | 1/26/2010 | 1/26/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, ric ok, p/s u/g n ok, no esc this project
|
Rough-In Permanent Service | 1/22/2010 | 1/25/2010 | 1/25/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called, left correction notice, NEC 110.12(B) there shall be no damaged parts- lug screw in meter base, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members-kitchen, 210.52(A)(1) receptacles shall be spaced such that no point along wall line is over 6' from an outlet-kitchen, BCC address shall be posted
|
Application received | | | 1/22/2010 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|