Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE10-00144
StatusFinaled
Name TRADITIONAL ELECTRIC
Site Address 3167 S ROOKERY LN
Project Name 
Customer Number 
ePlanReview 
Description
Temporary Power Pole
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service1/26/20101/27/20101/27/2010APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman corrections made, t/s u/g n ok, no esc this project
Temporary Service1/25/20101/26/20101/26/2010AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman called, left correction notice, same comments ele10-00145, NEC 406.8(B) 15 and 20a non-locking receptacles shall be listed weather resistant type, 312.5 conductors entering enclosures shall be protected from abrasion, 110.12(B) enclosures and equipment shall not be broken or contaminated by foreign materials, 250.53(G) upper end of electrode shall be flush with or below ground, BCC job id sticker shall be posted, address shall be posted, fee due
Reinspection Fee (no hold)1/26/20101/26/20101/26/2010APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman see fail comments
Application received  1/25/2010 DONE
This permit was created on the web by Emmet Bushman