Temporary Service | 1/26/2010 | 1/27/2010 | 1/27/2010 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman corrections made, t/s u/g n ok, no esc this project
|
Temporary Service | 1/25/2010 | 1/26/2010 | 1/26/2010 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman called, left correction notice, same comments ele10-00145, NEC 406.8(B) 15 and 20a non-locking receptacles shall be listed weather resistant type, 312.5 conductors entering enclosures shall be protected from abrasion, 110.12(B) enclosures and equipment shall not be broken or contaminated by foreign materials, 250.53(G) upper end of electrode shall be flush with or below ground, BCC job id sticker shall be posted, address shall be posted, fee due
|
Reinspection Fee (no hold) | 1/26/2010 | 1/26/2010 | 1/26/2010 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman see fail comments
|
Application received | | | 1/25/2010 | | DONE |
|
|
|
This permit was created on the web by Emmet Bushman
|