Final | 3/1/2010 | 3/2/2010 | 3/2/2010 | A | PASS |
Bob Reichert
|
|
|
Mike Phone #: ###-#### corrections made, ok to final, signed card, no esc
|
Final | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | FAIL |
Bob Reichert
|
|
|
mike Phone #: ###-#### met contractor, correction notice,BCC4-05-33(A)(B) mixer and icemaker shall be listed by a nationally recognized testing laboratory, NEC 210.63 shall provide showroom receptacles, corrections shall be made within 5 working days or further action will be taken
|
Override - Parcel Holds | 3/1/2010 | 1/1/1900 | 3/1/2010 | | |
|
|
|
Electrical final
|
Override - Parcel Holds | 3/1/2010 | 1/1/1900 | 3/1/2010 | | |
|
|
|
ele
|
Conference | 2/26/2010 | 2/26/2010 | 2/26/2010 | P | DONE |
Bob Reichert
|
|
|
Mike Phone #: ###-#### talked about pre-final like gfci in kitchen and disconnects for dw and hw heater, no esc this project
|
Override - Parcel Holds | 2/26/2010 | 1/1/1900 | 2/26/2010 | | |
|
|
|
conference inspection
|
Electrical Rough-In | 2/1/2010 | 2/3/2010 | 2/3/2010 | A | PASS |
Doug A Poedy
|
|
|
mike Phone #: ###-####. Ok to cover.
|
Application received | | | 2/1/2010 | | |
|
|
|
|
Issue permit | | | 2/1/2010 | | DONE |
|
|
|
|
First Notice | 3/2/2010 | 3/2/2010 | | | |
Bob Reichert
|
|
|
|