First Notice | 4/9/2010 | 4/9/2010 | 4/11/2011 | | DONE |
Doug A Poedy
|
|
|
This permit finaled on the web by Justin Frates
|
Final | 4/9/2010 | 4/9/2010 | 4/9/2010 | A | PASS |
Doug A Poedy
|
|
|
|
Final | 3/9/2010 | 3/10/2010 | 3/10/2010 | A | PART |
Jack Frank
|
|
|
Jack, we put sticky notes on the x-ray machines so you could easily see the UL listing. Thanks again for your help. Inspection requested from web by: Justin Frates Phone #: ###-#### 1 xray unit not listed called manufacturer's label states ul classified , but there is no UL mark or label
|
Electrical Rough-In | 2/25/2010 | 2/25/2010 | 2/26/2010 | P | PASS |
Jack Frank
|
|
|
The rough in inspection is for the ceiling. If it is satisfactory can we also get a final for the project. Walls and ceiling. Inspection requested from web by: Justin Fratesok
|
Final | 2/26/2010 | 2/26/2010 | 2/26/2010 | A | PART |
Jack Frank
|
|
|
. Inspection requested from web by: Justin Frates t/o ok no card still needs both xray units installed before final can be done
|
Electrical Rough-In | 2/18/2010 | 2/18/2010 | 2/18/2010 | P | PASS |
Jack Frank
|
|
|
Jack, you met with Stuart yesterday and he fixed the problem areas you showed him. So we told them it''s ok to cover. Thanks for your patience. Justin Inspection requested from web by: Justin Frates Phone #: ###-#### all walls ok no ceiling
|
Electrical Rough-In | 2/16/2010 | 2/17/2010 | 2/17/2010 | A | PART |
Jack Frank
|
|
|
Inspection requested from web by: Justin Frates Phone #: ###-#### corr. 517.13 switch in patient area and 11/4" for cables and holes cover ok 2 rms Brewster side, the other areas ok when ele contr corrects violation
|
Electrical Rough-In | 2/13/2010 | 2/16/2010 | 2/16/2010 | A | FAIL |
Jack Frank
|
|
|
Inspection requested from web by: Justin Frates Phone #: ###-#### called 300.4 shall provide 11/4" for cables all locations, seal all unused KOs, 517.13 use approved cables or raceways for medical x-ray wiring, note ceiling not ready walls failed do not cover posted
|
Electrical Rough-In | 2/12/2010 | 2/12/2010 | 2/12/2010 | P | CANC |
Doug A Poedy
|
|
|
Inspection requested from web by: Justin Frates. Please call back in. Unable to get to today due to overwelming requests. Leave your number. Number listed is your old partners.
|
Electrical Rough-In | 2/9/2010 | 2/10/2010 | 2/10/2010 | A | FAIL |
Doug A Poedy
|
|
|
Inspection requested from web by: Justin Frates Phone #: ###-####. Mutiple straping issues. Walls already covered and need opened up.
|
Application received | | | 2/9/2010 | | DONE |
|
|
|
This permit was created on the web by Justin Frates
|