Final | 3/29/2010 | 3/30/2010 | 3/30/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### corrections made, ok to final
|
Final | 3/29/2010 | 3/29/2010 | 3/29/2010 | P | FAIL |
Jack Frank
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### no power to some outlets called
|
Electrical Rough-In | 3/1/2010 | 3/2/2010 | 3/2/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### corrections made, ric ok
|
Rough-In Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17 conductors entering boxes shall be protected from abrasion-garage lights, 314.14 shall not exceed box fill for garage lights, NOTE: corrections shall be made within 5 working days or further action will be taken
|
Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### p/s u/g n ok
|
Rough-In Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 | A | NR |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### saw electrician, not done, see fee due
|
Reinspection Fee (no hold) | 3/1/2010 | 3/1/2010 | 3/1/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see nr
|
Electrical Rough-In | 2/11/2010 | 2/11/2010 | 2/11/2010 | P | PASS |
Bob Reichert
|
|
|
Concrete over ufer ground, ¾ conduit from house to garage underground. Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to backfill concrete encased electrode
|
Electrical Rough-In | 2/10/2010 | 2/11/2010 | 2/11/2010 | P | CANC |
Jack Frank
|
|
|
concrete poured over 20'' of ufer ground Inspection requested from web by: TOM BICANDI Phone #: ###-#### Inspection cancelled from web by: TOM BICANDI
|
Electrical Rough-In | 2/10/2010 | 2/11/2010 | 2/11/2010 | A | PASS |
Doug A Poedy
|
|
|
ufer ground Inspection requested from web by: TOM BICANDI Phone #: ###-####. Ok to encase.
|
Electrical Rough-In | 2/10/2010 | 2/10/2010 | 2/10/2010 | P | FAIL |
Bob Reichert
|
|
|
20'' ufer ground along footing. Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, left correction notice, NEC 250.52(A)(3) concrete encased electrode shall be encased with 2" concrete and with direct contact with earth, NOTE: corrections shall be made within 5 working days or further action will be taken
|
Application received | | | 2/10/2010 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|