Final | 4/5/2010 | 4/6/2010 | 4/6/2010 | A | PASS |
Bob Reichert
|
|
|
ryan Phone #: ###-#### corrections made, ok to final
|
Final | 4/5/2010 | 4/5/2010 | 4/5/2010 | A | FAIL |
Bob Reichert
|
|
|
###-#### Inspection requested from web by: Todd Holbrook called, left correction notice, NEC 250.94 shall provide intersystem bonding bar, 408.4 shall provide clear and concise circuit directory, 210.8(A)(3) front outdoor receptacle shall be gfci protected, 210.52 shall provide receptacle along bar, BCC all receptacles shall operate-garage, NOTE corrections shall be made in 5 working days or further action will be taken, such as removal of power
|
Rough-In Permanent Service | 2/16/2010 | 2/16/2010 | 2/16/2010 | A | PASS |
Bob Reichert
|
|
|
###-#### Inspection requested from web by: Todd Holbrook ric ok, p/s o/h n ok, 2 meters required
|
Application received | | | 2/16/2010 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|