Temporary Service | 2/22/2010 | 2/22/2010 | 2/22/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### corrections made, t/s u/g n ok, no esc this project
|
Temporary Service | 2/19/2010 | 2/22/2010 | 2/22/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, left correction notice, NEC 250.24 grounding electrode conductor shall be connected to grounded service conductor, 406.8(B) 15 and 20a receptacles shall be listed weather resistant type, BCC address shall be posted, job id sticker shall be posted, NOTE corrections shall be made within 5 working days or further action will be taken, no esc this project
|
Temporary Service | 2/19/2010 | 2/22/2010 | 2/22/2010 | A | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### duplicate request
|
Reinspection Fee (no hold) | 2/22/2010 | 2/22/2010 | 2/22/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see fail
|
Application received | | | 2/19/2010 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|