Permit Information
Permit NumberELE10-00405
StatusFinaled
Name MOUNTAIN VALLEY ELECTRIC
Site Address 561 N BALMORAL RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/13/20107/14/20107/14/2010APASS
DetailsBob Reichert
Key under mat Phone #: ###-#### >> Inspection requested via web by Dan Rohl ok to final
Final7/13/20107/13/20107/13/2010PNR
DetailsBob Reichert
Key under mat Phone #: ###-#### >> Inspection requested via web by Dan Rohl missing receptacles, plates, loose receptacles, panel schedule
Electrical Rough-In3/9/20103/10/20103/10/2010APASS
DetailsBob Reichert
Key under mat Inspection requested from web by: Dan Rohl Phone #: ###-#### corrections made, ric ok, no esc this project
Electrical Rough-In3/1/20103/2/20103/2/2010AFAIL
DetailsBob Reichert
Key under mat Inspection requested from web by: Dan Rohl Phone #: ###-#### called, left correction notice, NEC 300.4A&D edge of bored holes and nm cable and raceways shall be 1 1/4" from edge of framing members, 334.30 nm cable shall be stapled within 8" of box and not be stapled on edge, 110.26(F)(1) there shall be no piping in dedicated space over panel, BCC shall install fixtures and boxes for ri- down stairs and outside recpt, NOTE corrections shall be made within 5 working days or further action will be taken
Application received  3/1/2010 DONE
This permit was created on the web by Dan Rohl