Final | 4/29/2010 | 4/30/2010 | 4/30/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### called, ok to final
|
Permanent Service | 3/16/2010 | 3/17/2010 | 3/17/2010 | A | PASS |
Bob Reichert
|
|
|
The service is ready for inspection, any questions please call Terry at ###-####. thx. Inspection requested from web by: Stephen Kren Phone #: ###-#### p/s u/g n ok, 2 meters required- note: contractor to verify if 2" from transformer ok or requires 3"
|
Rough-In Permanent Service | 3/9/2010 | 3/10/2010 | 3/10/2010 | P | CANC |
Bob Reichert
|
|
|
Any questions please call Terry at ###-####, thx! Inspection requested from web by: Stephen Kren Phone #: ###-#### see ri, hold on service- can't have 2 services on one structure per NEC 230.2
|
Permanent Service | 3/10/2010 | 3/10/2010 | 3/10/2010 | P | FAIL |
Bob Reichert
|
|
|
Any questions please call Terry at ###-####, thx! Inspection requested from web by: Stephen Kren Phone #: ###-#### NEC 230.2, only one service per structure allowed
|
Electrical Rough-In | 3/10/2010 | 3/10/2010 | 3/10/2010 | P | PASS |
Bob Reichert
|
|
|
Any questions please call Terry at ###-####, thx! Inspection requested from web by: Stephen Kren Phone #: ###-#### ric ok
|
Application received | | | 3/4/2010 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|