First Notice | 4/26/2010 | 4/26/2010 | 5/27/2010 | | DONE |
Bob Reichert
|
|
|
|
Final | 4/26/2010 | 4/26/2010 | 4/26/2010 | P | PASS |
Bob Reichert
|
|
|
warren Phone #: ###-#### ok to final, will install rest of receptacles for roof-top at next phase, no esc this project
|
Final | 4/1/2010 | 4/2/2010 | 4/2/2010 | A | FAIL |
Bob Reichert
|
|
|
Warren-Please call at least 45 mins prior so he can get you access Phone #: ###-#### met contractor, left correction notice, NEC 210.63 shall provide gfci receptacles within 25' of a/c rooftop units, 110.12(A) shall close unused openings in disconnect and panel, 110.26 shall provide and maintain workspace about equipment, BCC no violations shall be retained, NOTE: corrections shall be made within 10 working days or further action will be taken, no esc this project
|
Application received | | | 3/12/2010 | | |
|
|
|
|
Issue permit | | | 3/12/2010 | | DONE |
|
|
|
|