Final | 5/11/2010 | 5/11/2010 | 5/11/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### ok to final
|
Electrical Rough-In | 3/22/2010 | 3/23/2010 | 3/23/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### corrections made ric ok
|
Rough-In Permanent Service | 3/22/2010 | 3/22/2010 | 3/22/2010 | P | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### see ri and p/s
|
Permanent Service | 3/22/2010 | 3/22/2010 | 3/22/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 3/22/2010 | 3/22/2010 | 3/22/2010 | P | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 cable in attic shall comply with 320.23, BCC shall provide all boxes and make-up, NOTE: corrections shall be made within 5 working days
|
Application received | | | 3/22/2010 | | DONE |
|
|
|
This permit was created on the web by Emmet Bushman
|