Permit Information
Permit NumberELE10-00594
StatusFinaled
Name TRADITIONAL ELECTRIC
Site Address 3193 S ROOKERY LN
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/20/20105/20/20105/20/2010PPASS
DetailsBob Reichert
Inspection requested from web by: Emmet Bushman Phone #: ###-#### ok to final
Permanent Service5/19/20105/19/20105/19/2010PCANC
DetailsBob Reichert
Inspection on outlet for sprinkler time clock. Inspection requested from web by: Emmet Bushman Phone #: ###-#### called contractor, told that he must get a separate permit, watch for service equipment and grounding
Permanent Service4/1/20104/1/20104/1/2010PPASS
DetailsBob Reichert
p/s u/g n ok
Electrical Rough-In3/25/20103/25/20103/25/2010APASS
DetailsBob Reichert
Inspection requested from web by: Emmet Bushman Phone #: ###-#### corrections made, ri ok
Rough-In Permanent Service3/24/20103/24/20103/24/2010AFAIL
DetailsBob Reichert
Inspection requested from web by: Emmet Bushman Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide at least 6" free conductor length in box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 210.52(A)(1)(2) shall provide receptacle in wall over 2' and such that no point is over 6' from outlet along wall line, NOTE corrections shall be made in 5 working days
Application received  3/24/2010 DONE
This permit was created on the web by Emmet Bushman