Final | 5/20/2010 | 5/20/2010 | 5/20/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### ok to final
|
Permanent Service | 5/19/2010 | 5/19/2010 | 5/19/2010 | P | CANC |
Bob Reichert
|
|
|
Inspection on outlet for sprinkler time clock. Inspection requested from web by: Emmet Bushman Phone #: ###-#### called contractor, told that he must get a separate permit, watch for service equipment and grounding
|
Permanent Service | 4/1/2010 | 4/1/2010 | 4/1/2010 | P | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 3/25/2010 | 3/25/2010 | 3/25/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### corrections made, ri ok
|
Rough-In Permanent Service | 3/24/2010 | 3/24/2010 | 3/24/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Emmet Bushman Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide at least 6" free conductor length in box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 210.52(A)(1)(2) shall provide receptacle in wall over 2' and such that no point is over 6' from outlet along wall line, NOTE corrections shall be made in 5 working days
|
Application received | | | 3/24/2010 | | DONE |
|
|
|
This permit was created on the web by Emmet Bushman
|