Final | 5/4/2010 | 5/5/2010 | 5/5/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### called, ok to final
|
Rough-In Permanent Service | 3/30/2010 | 3/31/2010 | 3/31/2010 | A | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### wrong type request, see ri
|
Electrical Rough-In | 3/31/2010 | 3/31/2010 | 3/31/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### corrections made, ric ok
|
Rough-In Permanent Service | 3/30/2010 | 3/30/2010 | 3/30/2010 | P | CANC |
Bob Reichert
|
|
|
Any questions please call, thx. Inspection requested from web by: Stephen Kren Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 3/30/2010 | 3/30/2010 | 3/30/2010 | P | FAIL |
Bob Reichert
|
|
|
Any questions please call, thx. Inspection requested from web by: Stephen Kren Phone #: ###-#### called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.23 shall protect nm cable within 6' of attic access, NOTE corrections shall be made within 5 working days
|
Permanent Service | 3/30/2010 | 3/30/2010 | 3/30/2010 | P | PASS |
Bob Reichert
|
|
|
Any questions please call, thx. Inspection requested from web by: Stephen Kren Phone #: ###-#### p/s u/g n ok
|
Application received | | | 3/26/2010 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|