Permit Information
Permit NumberELE10-00680
StatusFinaled
Name NORTHWEST ELECTRICAL
Site Address 775 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: New Credit Union building
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/15/20109/16/20109/17/2010APASS
DetailsDoug A Poedy
Phone #: ###-#### >> Inspection requested via web by Mark Sessions
DOC - Permit Finaled9/17/20109/17/20109/17/2010PPASS
DetailsDoug A Poedy
Final9/13/20109/14/20109/15/2010PPART
DetailsDoug A Poedy
Phone #: ###-#### >> Inspection requested via web by Mark Sessions.Rooftop needs ko seal, wr gfci's, and smaller fuses on small rooftop unit. Inside needs duplex plate in safe and recepts checked in room to left of safe. Still needs exterior walk around.
Electrical Rough-In8/30/20108/31/20108/31/2010APASS
DetailsBob Reichert
Ceiling Phone #: ###-#### >> Inspection requested via web by Mark Sessions ok cover ceiling
Electrical Rough-In8/26/20108/26/20108/26/2010APASS
DetailsBob Reichert
ceiling inspection Phone #: ###-#### >> Inspection requested via web by Mark Sessions ok cover canopy ceiling
Electrical Rough-In8/20/20108/23/20108/23/2010APASS
DetailsBob Reichert
Reinspection of broken flex. Later in the morning if you can please. Phone #: ###-#### >> Inspection requested via web by Mark Sessions corrections made, ok cover ceilings
Electrical Rough-In8/20/20108/20/20108/20/2010PFAIL
DetailsDoug A Poedy
ceiling Phone #: ###-#### >> Inspection requested via web by Mark Sessions. NEC 314.23d, NEC 348.30, NEC 358.30b. Repair broken flex.
Permanent Service7/28/20107/28/20107/28/2010PPASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Mark Sessions p/s u/g n ok
Electrical Rough-In7/1/20107/1/20107/1/2010PPASS
DetailsBob Reichert
Inspection requested from web by: Mark Sessions Phone #: ###-#### ri ok for walls, soffits in and out, hard lids
Electrical Rough-In5/14/20105/14/20105/14/2010PPASS
DetailsBob Reichert
underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g parking lot
Electrical Rough-In5/13/20105/14/20105/14/2010APASS
DetailsBob Reichert
underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g north and middle parking lot
Electrical Rough-In5/11/20105/12/20105/12/2010APASS
DetailsBob Reichert
underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g north and east of building
Electrical Rough-In4/23/20104/23/20104/23/2010PPASS
DetailsDoug A Poedy
Grounding Inspection requested from web by: Mark Sessions Phone #: ###-####
Electrical Rough-In4/20/20104/21/20104/21/2010APASS
DetailsBob Reichert
underslab branch circuit rough-in Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover slab inside building
Electrical Rough-In4/20/20104/20/20104/20/2010APASS
DetailsBob Reichert
U/G Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g in building going north towards canopy, will see outside later
Electrical Rough-In4/15/20104/16/20104/16/2010APASS
DetailsBob Reichert
Underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g from transformer to entering building for service panels
Electrical Rough-In4/2/20104/5/20104/5/2010APASS
DetailsBob Reichert
Uffer, and sleeves. Early inspection please if possible. Inspection requested from web by: Mark Sessions Phone #: ###-#### grounding electrode and conductor, sleeves ok to cover
Application received  4/2/2010 DONE
This permit was created on the web by Mark Sessions
First Notice9/17/20109/17/2010   
DetailsDoug A Poedy
First Notice9/17/20109/17/2010   
DetailsDoug A Poedy