First Notice | 4/9/2010 | 4/9/2010 | 11/15/2010 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Debby Ellis
|
Temporary Service | 4/9/2010 | 4/9/2010 | 4/9/2010 | P | PASS |
Bob Reichert
|
|
|
Pat Gill ###-#### Inspection requested from web by: Debby Ellis Phone #: ###-#### corrections made, t/s o/h n ok, no esc this project
|
Temporary Service | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | NH |
Jack Frank
|
|
|
Inspection requested from web by: Debby Ellis Phone #: ###-#### called left message no access gate locked
|
Final | 4/6/2010 | 4/6/2010 | 4/6/2010 | P | FAIL |
Bob Reichert
|
|
|
Pat Gill is good contact at ###-####, vacant lot by Tate Rents, temp pwr pole final Inspection requested from web by: Debby Ellis Phone #: ###-#### called, left correction notice, NEC 312.5 shall provide abrasion protection for all conductors entering enclosure, 406.8(B) receptacle shall be listed weather resistant, 110.12(A) shall close all unused openings, 408.4 shall provide circuit directory, 358.30 shall strap emt within 3' of fitting, BCC shall post job id sticker, NOTE: corrections shall be made within 5 working days or further action will be taken, call for t/s, not final next time
|
Application received | | | 4/6/2010 | | DONE |
|
|
|
This permit was created on the web by Debby Ellis
|