Final | 8/24/2010 | 8/25/2010 | 8/25/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov corrections made, ok final
|
Final | 8/21/2010 | 8/23/2010 | 8/23/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, too many corrections to write, gave over phone to contractor, strap riser, check for clearance for service disconnect, identify service disconnect, provide bonding bar per NEC 250.94, kitchen island gfci shall operate, shall provide convenience receptacle in island, wire disposal, tighten loose receptacles in hall, coat rack, m bath
|
Permanent Service | 5/17/2010 | 5/17/2010 | 5/17/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 5/11/2010 | 5/11/2010 | 5/11/2010 | P | NR |
Bob Reichert
|
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-#### met electrician, shall recall and turn line and load around
|
Electrical Rough-In | 5/10/2010 | 5/10/2010 | 5/10/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-#### corrections for ri only made, ric ok
|
Rough-In Permanent Service | 5/5/2010 | 5/6/2010 | 5/6/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-#### called, left correction notice, NEC 250.94 shall provide intersystem bond bar, 250.92 shall provide bond bushings, 314.4 shall ground metal boxes, 314.20 boxes shall be flush with finished surface of combustible material, 314.16 shall provide free space for conductors-box fill-metal box, 230.6 service conductors considered outside when encased in 2" concrete, NOTE: corrections shall be made in 5 working days or further action will be taken
|
Application received | | | 5/5/2010 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|