Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE10-00971
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 2268 N PLEASANT HILL WAY
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: new house wiring
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/24/20108/25/20108/25/2010PPASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by daniel bibikov corrections made, ok final
Final8/21/20108/23/20108/23/2010PFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, too many corrections to write, gave over phone to contractor, strap riser, check for clearance for service disconnect, identify service disconnect, provide bonding bar per NEC 250.94, kitchen island gfci shall operate, shall provide convenience receptacle in island, wire disposal, tighten loose receptacles in hall, coat rack, m bath
Permanent Service5/17/20105/17/20105/17/2010PPASS
DetailsBob Reichert
Inspection requested from web by: daniel bibikov Phone #: ###-#### p/s u/g n ok
Electrical Rough-In5/11/20105/11/20105/11/2010PNR
DetailsBob Reichert
Inspection requested from web by: daniel bibikov Phone #: ###-#### met electrician, shall recall and turn line and load around
Electrical Rough-In5/10/20105/10/20105/10/2010PPASS
DetailsBob Reichert
Inspection requested from web by: daniel bibikov Phone #: ###-#### corrections for ri only made, ric ok
Rough-In Permanent Service5/5/20105/6/20105/6/2010AFAIL
DetailsBob Reichert
Inspection requested from web by: daniel bibikov Phone #: ###-#### called, left correction notice, NEC 250.94 shall provide intersystem bond bar, 250.92 shall provide bond bushings, 314.4 shall ground metal boxes, 314.20 boxes shall be flush with finished surface of combustible material, 314.16 shall provide free space for conductors-box fill-metal box, 230.6 service conductors considered outside when encased in 2" concrete, NOTE: corrections shall be made in 5 working days or further action will be taken
Application received  5/5/2010 DONE
This permit was created on the web by daniel bibikov